Base shear calculation
sazeh computes the base shear of a building from the .e2k file of its ETABS model under clause 3-3-1 of the seismic code: the seismic coefficient C = A·B·I / Ru, the base shear V = C·W, and the floor V ≥ 0.12·A·I·W. Every term of this chain is printed on the calculation sheet with its clause number, and the base shear that the analysis of the model actually reaches is compared with this value.
The terms
| Term | How sazeh takes it |
|---|---|
A | From the project's city in the Persian edition, or one of four values in the English edition (design base acceleration A) |
B | B = B1·N. B1 is built from the soil type, the hazard band and the period, and N rises above 1 for a period longer than Ts |
I | The importance factor, from the occupancy group of the building |
Ru | From the row of the structural system in table 3-4; a system whose row is not implemented does not borrow a neighbour's factor |
T | The empirical period T = α·H^k, clause 3-3-3 |
W | The seismic weight: the dead load plus a share of the live load from table 3-1 |
The period
The equivalent static base shear is built with the empirical period. Its coefficients are α = 0.05 and k = 0.9 for a concrete moment frame, α = 0.08 and k = 0.75 for a steel moment frame, and α = 0.05 and k = 0.75 for the dual wall-frame system. The analytical period from the modal analysis is compared with the cap of 1.25 times the empirical period, and that comparison is a row of its own on the sheet.
Seismic weight and the model's mass source
The seismic weight is built from the weight of the members, slabs and walls of the model and from its dead and live loads. The live-load share is 20% for most occupancies, at least 40% for libraries and storage and 100% for a tank. This weight is then compared with the mass source of the ETABS model itself. If the mass source takes a smaller share of the live load, or its weight differs from the code weight by more than 5%, the clause is reported as not met, because a model that leaves out part of the mass understates the base shear of the whole building.
The minimum base shear
Under clause 3-3-1-1 (equation 3-3) the base shear is never less than 0.12·A·I·W. The sheet says which of the two governs, and also compares the base shear of the model's analysis with this floor.
Distribution over the height and accidental torsion
Under clause 3-3-6 the base shear is distributed over the storeys by Fi = wi·hi^k / Σ(wj·hj^k) · V, where k is 1 for a period up to 0.5 s, 2 for 2.5 s and above, and linear in between. The force of every storey is applied with an accidental eccentricity of 5% under clause 3-3-7.
What does the sheet print?
B1, N and C each get an information row with their clause number, so that an engineer can compare them with their own calculation. The base shear row compares the base shear of the model's analysis with the code V. If the seismic load patterns of the model carry no load and the analysis gives no base shear, the row stays "deferred" and is never reported as met.
What is the right mass source for a residential building?
For a residential building the seismic weight is the self weight and the dead load plus 20% of the live load. Roofs enter with 20% only in zones of high, heavy and very heavy snow; elsewhere table 3-1 gives the roof no share. sazeh currently applies the live-load share of the occupancy to a roof live-load pattern. In ETABS this means a mass source with a factor of 1 on the dead and superimposed dead patterns and 0.2 on the live patterns. If the self weight is taken from the elements, do not repeat it in the loads.
sazeh reads the mass source of the model from the .e2k file, computes the weight the model builds with it and compares it with the weight of the code table. If the live factor is below the share in the table, the row names that factor. If the model defines no mass source, the row stays "deferred".
How do the minimum base shear and response-spectrum scaling work?
Under clause 3-3-1-1 (equation 3-3) the minimum base shear is 0.12·A·I·W. The base shear of a response-spectrum analysis must be at least a fraction of the equivalent static base shear: under clause 3-4-1-4 it is 0.85 for a regular building, 0.90 for an irregular one, and 1.0 when the irregularity is an extremely weak storey, an extremely soft storey or extreme torsion. sazeh applies only 0.85 and 0.90, does not yet apply the 1.0 case, and treats a building that has not been declared regular as irregular. If the spectral base shear is below this floor, every spectral result has to be multiplied by the scale factor. If it is above, it is not reduced.
When the model has a response-spectrum case, sazeh builds the spectral base shear of each direction from its own modes by CQC, compares it with the floor and prints the required scale factor on an information row. The model's own scale factor (SF) is also read and printed. sazeh does not deliver scaled spectral results; the row is an instruction to apply in ETABS. If the model has a spectrum case but no modal analysis was run, the row stays "deferred".
Check this on your own model
Upload the .e2k file on the upload page. The sheet prints the seismic weight of every storey, the comparison of the mass source with the code table, B1, N, C, the base shear floor, the comparison of the analysis base shear with them and, if the model has a spectrum case, the scale factor. The response modification factor and a worked example are on the seismic coefficient page.
Is there an Excel sheet for the base shear?
No. The output of sazeh is a printable A4 calculation sheet that carries all of these numbers with their clause numbers.
Related pages
- Design base acceleration A
- Response modification factor and seismic coefficient
- Structural calculation
- Storey drift check
- Limitations